電纜橋架的規(guī)格如何選擇?
玻璃鋼電橋架在我們的日常生活中應(yīng)用如此廣泛,規(guī)格種類也是紛繁復(fù)雜多樣,這就給我們在規(guī)格選擇留下了一個難題。那么,電纜橋架的規(guī)格到底該如何選擇呢?
FRP electric bridge is widely used in our daily life, and the specifications are also complex, which leaves us a difficult problem in the selection of specifications. So, how to choose the specification of cable tray?
一、規(guī)格的選擇
1、 Selection of specifications
1、橋架的寬度和高度就按公認的表格選擇,并應(yīng)符合電纜填充率不超過有關(guān)標準規(guī)范的規(guī)定值,動力電纜可取40-50%,控制電纜可取50-70%,另外需予留10-25%的式程可供發(fā)展余量。
1. The width and height of the cable tray shall be selected according to the recognized official form, and the cable filling rate shall not exceed the specified value of relevant standards and specifications. The power cable can be 40-50%, the control cable can be 50-70%, and 10-25% margin shall be reserved for development.

2、各種彎通及附件規(guī)格應(yīng)符合工程布置條件并與玻璃鋼電纜橋架相配套。
2. The specifications of various bends and accessories shall meet the engineering layout conditions and be matched with FRP cable tray.
3、支、吊架規(guī)格的選擇,應(yīng)按橋架規(guī)格、層數(shù)、跨距等條件配置。并應(yīng)滿足荷載的要求。
3. The specifications of supports and hangers shall be selected according to the specifications, layers and spans of the bridge. And it should meet the load requirements.
4、橋架橫截面積的選擇見規(guī)范表。
4. The selection of bridge cross-sectional area is shown in the official specification table.
二、支、吊架的配置選擇
2、 Selection of support and hanger configuration
1、戶內(nèi)支、吊短跨距一般采取1.5-3m。戶外立柱中跨距一般采取6m。
1. The short span of indoor support and hoisting is generally 1.5-3m. The middle span of outdoor column is generally 6m.
2、非直線段的支、吊架配置就遵循以下原則:當玻璃鋼電纜橋架寬度<300mm時,應(yīng)在距非直線段與直線結(jié)合處300-600m的直線段側(cè)設(shè)置一個支、吊架。當玻璃鋼電纜橋架寬度>300mm時,除符合相關(guān)條件外,在非直線段中部還應(yīng)增設(shè)一個支、吊架。
2. The support and hanger configuration of non-linear section shall follow the following principles: when the width of FRP cable tray is less than 300 mm, a support and hanger shall be set at the side of the straight section 300-600 m away from the joint of non-linear section and straight line. When the width of FRP cable tray is more than 300 mm, in addition to meeting the relevant conditions, a support and hanger should be added in the middle of the non-linear section.
3、橋架多層設(shè)置時層間距為200,250,300,350mm。
3. When the cable tray is set in multiple layers, the center distance between layers is 200250300350mm.
4、橋架直線段每隔50m應(yīng)予留伸縮縫20-30mm(金屬橋架)。
4. Expansion joints of 20-30mm (metal bridge) shall be reserved every 50m in the straight section of the bridge.
以上就是小編為大家介紹的關(guān)于電纜橋架規(guī)格內(nèi)容介紹,希望可以幫助到大家。
The above is a small series for you to introduce the cable tray specifications, hope to help you.
上一篇:電纜橋架碰到短路問題怎么辦
下一篇:電纜橋架選購要點介紹
下一篇:電纜橋架選購要點介紹
相關(guān)文章 / Recommended news
- 山東電纜橋架:電纜橋架系統(tǒng)中常見的問題之一是負載能力不足
- 濟南電纜橋架廠家:選錯橋架=白花錢?一圖看懂電纜橋架類型大全
- 山東電纜橋架:鋁合金橋架因其輕、強、耐腐蝕受到各種工程方的喜愛
- 濟南電纜橋架:如何根據(jù)實際需求選擇合適的橋架材質(zhì)和結(jié)構(gòu)?
- 山東電纜橋架:以冷軋鋼板制成的熱鍍鋅電纜橋架特別適合各種強酸、堿霧氣等強腐蝕環(huán)境使用
- 濟南電纜橋架:噴涂橋架和防火橋架因噴涂粉末不同造成用途不同
- 山東電纜橋架廠家:潮濕地區(qū)使用不銹鋼電纜橋架是不錯的選擇
- 濟南電纜橋架:不同材質(zhì)的電纜橋架各自有哪些性能特點
- 山東電纜橋架:潮濕環(huán)境如地下室衛(wèi)生間該選哪種材質(zhì)的橋架
- 電纜橋架是什么?主要用于哪些場景?